Two system heating maintenance Basement system York 2 stage 96% efficient furnace Pulled and cleaned flame sensor Condensate trap is integral to the collector box Aprilaire 600 humidifier operating normally. No water leaks at this time Water panel is in good condition Cleaned Trane CleanEffects electronic air cleaner with shopvac and brush High fire gas pressure was 4"wc, spec is 3.5. Dialed it back to 3.5" Temp rise 50⁰ Low fire was 2"wc, spec is 1.5" Dialed back to 1.5 Temp rise 40⁰ Attic system York 2 stage 96% Cleaned trane electronic air cleaner Disabled humidifier from operating. There is no auxiliary drain pan underneath it Cleaned flame sensor Wired thermostat for two stage heat operation. Gas pressure 3.5" high fire temp rise 43⁰ Low fire 1.5" Temp rise 41⁰

Two system heating maintenance

Basement system 
York 2 stage 96% efficient furnace
Pulled and cleaned flame sensor
Condensate trap is integral to the collector box
Aprilaire 600 humidifier operating normally.  No water leaks at this time
Water panel is in good condition
Cleaned Trane CleanEffects electronic air cleaner with shopvac and brush
High fire gas pressure was 4"wc, spec is 3.5.  Dialed it back to 3.5"
Temp rise 50⁰
Low fire was 2"wc, spec is 1.5"  Dialed back to 1.5
Temp rise 40⁰

Attic system
York 2 stage 96%
Cleaned trane electronic air cleaner
Disabled humidifier from operating.  There is no auxiliary drain pan underneath it
Cleaned flame sensor
Wired thermostat for two stage heat operation. 
Gas pressure 3.5" high fire temp rise 43⁰
Low fire 1.5" Temp rise 41⁰ Two system heating maintenance

Basement system 
York 2 stage 96% efficient furnace
Pulled and cleaned flame sensor
Condensate trap is integral to the collector box
Aprilaire 600 humidifier operating normally.  No water leaks at this time
Water panel is in good condition
Cleaned Trane CleanEffects electronic air cleaner with shopvac and brush
High fire gas pressure was 4"wc, spec is 3.5.  Dialed it back to 3.5"
Temp rise 50⁰
Low fire was 2"wc, spec is 1.5"  Dialed back to 1.5
Temp rise 40⁰

Attic system
York 2 stage 96%
Cleaned trane electronic air cleaner
Disabled humidifier from operating.  There is no auxiliary drain pan underneath it
Cleaned flame sensor
Wired thermostat for two stage heat operation. 
Gas pressure 3.5" high fire temp rise 43⁰
Low fire 1.5" Temp rise 41⁰