Cooling preventative maintenance performed Check filter - 2200 popup clean Check coil for any buildup or debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 45+5 @ 49.98 + 5.09 Check OD fan Amp - 0.57 252v Check compressor Amp - 6.41 284v Verify pressures and HP-SC/LP-SH 212-8/108-16 Delta T - 21° The Air handler and AC are in optimal running conditions.