1999 Waterfurnace premiere 2 geothermal two pump pressurized alcohol system Shop vac all equipment, water flush Alpine pure water furnace brand air filter, shut down humidifier controls and air damper for summer, water flush and scrub drain pan and drain trap, test alcohol antifreeze at 0.976 equivalent to +10° freeze protection, Meet with vector security systems technician to test accuracy of thermostat. Thermostat reading was within 0.8° of Fieldpiece stick thermometer Repressurize ground loops to 40 with house water *** One of two flow center pumps is locked up and needs replaced. Seth prepared estimate and sent via email but obtained verbal authorization while on site. Seth will order parts and Ashlea will follow up with scheduling