Cooling preventative maintenance performed BASEMENT Check filter - 20x25x1 clean Check coil for any buildup or debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD -40+5 @ 39.26+4.96 Check OD fan Amp - 0.56 Check compressor Amp - 5.62 Verify pressures and HP-SC/LP-SH 187-10°/100/11° Delta T - 20° The Air handler and AC are in optimal running conditions. Cooling preventative maintenance performed 2ND FLOOR Check filter -16x25x4 clean Check coil for any buildup or debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD -35+5 @ 34.75+4.95 Check OD fan Amp - 0.61 Check compressor Amp - 3.15 Verify pressures and HP-SC/LP-SH 177-6/107-9 Delta T - 24° The Air handler and AC are in optimal running conditions.