Trane XV95 2014 has a failed integrated furnace ignition control module preventing the blower and heat mode from running in any stages. The outdoor condenser turns on because of a direct 24 volt connection between the thermostat and the outdoor unit Confirmed blower operation with GE Techmate XL Seth will contact homeowners with estimate after parts availability and cost are verified on Friday morning 5-23-25