Cooling preventative maintenance performed Check filter -16x25x1 new today Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD -45+5 @ 45+5 Verify pressures and HP-SC/LP-SH Delta T - 18° The Air handler and AC are in optimal running conditions.