Performed cooling maintenance Replaced 20x25x4 filter with one provided with the gold maintenance plan Blower is OK Evaporator coil is clean Drain is clear Adjusted blower speed to match capacity of AC Closed humidifier bypass damper Refrigerant charge good: 10⁰ subcool Tore down and washed Condenser coil Capacitor tested 57/5mfd 23⁰ temperature drop across evaporator coil System operating within factory specifications at this time.