Condenser coil 75% damaged due to what appears to be a power washer System running very high head pressure as a result Capacitor tested OK Cause for outdoor fan motor stopping is likely due to overheating from the damaged coil and the unit getting too hot System has a history of refrigerant leaks, service record on the ductwork from 2014 shows 1lb of r22 and leak sealant added Exhaust and intake are incorrectly pitched

Condenser coil 75% damaged due to what appears to be a power washer 
System running very high head pressure as a result
Capacitor tested OK
Cause for outdoor fan motor stopping is likely due to overheating from the damaged coil and the unit getting too hot
System has a history of refrigerant leaks, service record on the ductwork from 2014 shows 1lb of r22 and leak sealant added
Exhaust and intake are incorrectly pitched