2001 Yrane XB 2 ton original to the house system is running in fair to good condition considering the age. The furnace was serviced in October by Brandon with a replacement blower capacitor. Today's indoor services included a drain flush, cooling system run test with 55 supply temperature and minor safety inspection inside. The outdoor equipment is running in fair to good condition with the power supply perfectly on point at 34.9 and 3.9 spec'd at 35 + 4 +/- 6% Running refrigerant pressures are within temperature curve for a piston r22 coil with 83 outdoor and 71 indoor temperature The outdoor spiny fin condenser coil was matted over on all four sides and required a extra heavy duty water flush. Air filter is in acceptable condition and reinstalled. The thermostat is cooling properly with no concerns of the homeowner and batteries were replaced within a few months All equipment is clean safe and ready for summer