Climate master two system house. System A servicing basement and third floor with communicating zones is displaying service code 60 indicating general compressor malfunction. With submenu fault code 62 indicating high current draw at stardust on inverter compressor. System a will not run at all and enters an immediate lockout after a power cycle off and on. System A will require an additional 2 to 3 hours of electrical diagnostics to follow the proper procedures with tech support for inverter compressor diagnostics and inverter driver diagnostics System B servicing the middle level primary floor of the house is actively locked out on service code 6 indicating condensate overflow hard lockout. Confirmed 100% complete full blockage of the PVC drain pipe p-trap. Cleared blockage, flushed the drain, run test equipment in cooling mode from the first floor thermostat. System A will require 2 hours pre-approval during the hours of 9:00 a.m. and 5:00 p.m. eastern time for tech support