Upon arrival inspected air conditioner and found unit not cycling outside. Inspected electrical and found melted wires for capacitor. Replaced 70mfd capacitor and 7.5 capacitor with turbo 200x and test run system. System needed washed advised homeowner. Unit cooling at 9° subcool and 20° delta T