System locked out on high pressure Could not get the fault to clear Diagnosed pressure switch failed open Jumped out pressure switch Reset faults System operating At departure, noticed another fault Compressor temperature sensor fault Went through the wiring, found no issues Compared values to the service manual chart, sensor is way out of range. System is operating currently, despite the active Compressor dome temperature sensor fault We will return Friday afternoon to replace the temperature sensor and add a new pressure switch.