Preformed cooling maintenance. Upon arrival we tested start, run amps for the compressor and fan motors. All tested within manufactured specifications. Tested the contactor it did ohm out at the high side but still test within the manufacture specifications. Upon further inspection we did find that the ducts, plenums, blower wheel and condenser coils could benefit from a cleaning. Offered estimates for each cleaning. Unit was cooling upon departure.