Unit is short cycling,,,noticed a notification on one control board saying there was a communication error with compressor B1 ,,found the total of 6 bad fuses inside the unit,, 3 are connected to one compressor and the other 3 to other compressor,,, there is a total of 4 compressors inside the unit,, unfortunately 2 of them are not working,,, after replacement we will further diagnose the unit and verify proper operation.,,, will upload pictures. After fuse replacement we found one of the compressors bad (A1,,,open winding),, managed to get the unit up and running, however transducer/ high pressure switch need to be replaced as well,,office will call the customer to keep them updated.