1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor. 6. Checked compressor amp draw. 7. Checked condenser fan motor amp draw. 8. Inspected / replaced return filter. 9. Inspected return plenum for debris/ dirty. 10. Inspected evaporator coil. 11. Inspected blower motor/ blower wheel. 12. Checked blower amp draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Inspected drain lines and treated to prevent blockages 15. Washed condenser unit to promote heat exchange Found both emergency drain pans full of water. Upon further inspection we found that both drain lines are tied together and clogged. CLEAR DRAIN BLOCK - USING NITROGEN ONLY LEVEL 2 CONDENSATE DRAIN LINES NEED TO BE CLEANED OR THEY CAN CLOG WITH ALGAE AND DEBRIS Includes shop vacuuming when necessary and 1 PVC Coupling Al