I performed a single system cooling maintenance on a 2022 gas system. The system has labor warranty until 2033. I checked amps, capacitor, filter, electrical, drains, cleanliness, refrigerant temperature, and safeties. I investigated an issue with the thermostat, also. The thermostat has corrosion present in the contacts. I replaced the 45/7.5 capacitor and thermostat. The thermostat was replaced with a T4 pro. Both parts were replaced under parts/labor warranty per the office. System is cooling within manufacture specifications. I provided a price for a hard start kit due to the starting amps almost being at full load. 103/109. I observed that the wall outlet for the furnace is getting hot. Recommend replacing the outlet.