Today we visited to determine why the garage air handler has such a high static pressure. The machine is designed to have a maximum pressure of 0.50 in. W.C., but is operating at 1.10in. W.C. This high pressure has already caused a coil failure even though the unit is only three years old. The unit was moved from the attic and both the supply and return trunk lines are not sized for the proper volume of air. James put together a proper design and sent the estimate over to Mr. and Mrs. Mittelman. In addition to looking at the airflow issue James looked over the recent installation and the new Bosch unit is running great and ready for inspection.