View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-D6CBEE64B26C4EFBB0C50A7643C5708E Return to replace first floor igniter, Solenoid valve for first floor humidifier, Install neutralizer condensate pump on first floor system: Shut the equipment off at the thermostat at arrival Disconnected discharge line from existing condensate pump Removed existing condensate pump from system drainage, and throw away Installed and secured brand new neutralizer condensate pump to the side of the furnace Install new neutralizer minerals into the condensate pump reservoir redo Condensate piping- The second floor heat, and AC, First floor, heat, and AC, And humidifier all drain into this condensate pump Separate acidic from not acidic water And pipe into system Connect discharge line to new Condensate pump and strap power wire your neat and clean and plug-in Test The new neutralizer condensate pump and confirm normal operations and no leaks Remove the existing igniter from