View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-49440B0BF7E54B208F7EFB35C604D1B9 Customer has no heat from one of his Carrier gas fired furnaces: At arrival, the thermostat is calling for heating Check furnace and mechanical room- Found that the system was showing an error code of 31 Indicating issue with pressure switch / Inducer motor Try to reset furnace, but the error message comes right back after the 90 second blower on at start up try bypassing pressure switch- motor does not come on brought direct 120 to inducer motor to confirm the motor is operational control board replacement on carrier furnace is recommended The customer also has a water heater that is 23 years old. The Mechanical room is extremely tight and I don’t see how you would be able to get this Water Heater in or out. I believe there is old brass piping, connecting to the water heater and not copper. There is no pitch on the venting- With the existing set up, Plumbing and acces