View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-3CC6AB79AF0847179DAD5B3C3E1DBB63 Customer is having issues with steam boiler and second floor radiator and bathroom is not heating up: The customer also stated at arrival that A plumber had looked at the boiler and stated that the system was overfilling. * At arrival confirmed the water level in the steam boiler is at a normal level- okay * Drain water from steam boiler testing low water cut off an automatic water feeder- Normal operation operations * Call for heating from Honeywell T6 Wi-Fi thermostat- Boiler fires * Test water cut off again to make sure that it is shutting down the main burner and confirm it filled water level back to correct level in sight class * boiler fires: Monitor system operations * Quickly found that the boiler is surging and pulling water down to a low water scenario where the boiler shuts down and the auto feeder kicks in- Water level gets too high overtime * The system is su