View visual findings from this job here - https://visionshare.xoi.io/?id=XA-213F-A7ADF2BAF88B4679A3EBD8EEB67B3A1 Preform maintenance on peerless high-efficiency gas water boiler with six heating zones and indirect hot water storage tank + (3) aspen Hydro air handlers and (1) garage modine heater: GAS WATER BOILER: * shut power to system * removed boiler cover door * removed condensate and neutralizer kit from boiler * removed flame rod and spark igniter from boiler: Cleaned with copper bristle brush, and polished with steel wool- Reinstalled * Brought condensate and neutralizer kit Outside- Chemically sprayed and flushed clean with hose * Vacuumed and dusted out loads of debris from inside of boiler cabinet and components * Reinstalled and secured condensate and neutralizer kit back into boiler and connect to all drainage * install new neutralizer minerals inside of neutralizer kit * Secured and inspected all electrical wiring, and connections * Test and inspect expansion tank,
Return to make repairs on Crown gas water boiler ( expansion tank / air vent / boiler drain ) - shut power to boiler - Shut water feed to boiler - Close all supply and return ball valves - Drain down boiler - Removed the existing expansion tank, air vent and boiler drain - Pipe in and install brand new expansion tank, air vent and boiler drain and secure all connections - When installing the expansion tank, extend 1/2 piping and install elbow to drop tank from sideways to hanging - Support pipe with threaded rod, split rings hanger and base plate - Open water feed back to boiler and fill system and purge all air from boiler - Return power to system - Start with opening basement supply and return and call for heating at thermostat - boiler fires and circulator pump is on and running- monitor system operations, boiler pressure and temperature and confirm system satisfied at temp of 180 and supply / baseboard and return piping are all heating properly - Open all supply and return valv
View visual findings from this job here - https://visionshare.xoi.io/?id=XA-0013-7B771E990CF5490598A5A42271EA98D6 Preform maintenance on (1) Crown gas fired water boiler from 02/1998: shut power to the boiler at arrival Shut gas valve down and turn off pilot light Check the water, pressure and temperature in the boiler- Pressure gauge is reading zero Found the valve closed to the boiler supply water feed Dismantle burner section and removed all burners from the boiler Vacuum and brushed out all burners, clean and clear Vacuumed and dusted under boiler heat, exchanger, and burner section Vacuum and dusted boiler cabinet, piping and components, clean and clear Inspected heat exchanger / flue piping and damper motor- ok customer approved replacement of worn out thermocouple- removed existing and installed brand new Securing in pilot assembly, and gas valve Relight pilot- Stays lit first try Secure all electrical wiring, and components Open valve to water feed- Feeder begins filling boil