View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-9DBE7771B37A42C7A9F8622735B17EE8 Customer has no heat on the second floor of the home: * At arrival, check thermostat and found it satisfied at 54° * I called for Heating at the thermostat and raise the temperature to 65° * The indoor blower motor is on and running in the attic by the Hydro coil is cold * Check the circulator pump and boiler in the basement * Found that the second floor heating zone was not circulating hot water * I recommended bleeding the heating zone as a first step, but also gave the customer warning that the circulator pump may need to be replaced * She agreed to trying bleeding the second floor heating zone * purge 3 buckets of water from second floor heat zone- no air in system * hot water coming back- return power and test after bleeding - pump is still not circulating and extremely hot- bad pump * Customer agreed to circulator pump replacement * Isolated circulator pump and rem