Purchase 2025 geothermal annual maintenance plan Perform cooling inspection while on site today Waterfurnace Envision packaged geothermal equipment is in fair to poor condition but does appear to be holding the refrigerant pressures since the last visit. Equipment is confirmed to have refrigerant leaks in unknown possibly multiple locations in the past and has been treated with leak stop and dye. The air coil drain Pan has also been resealed multiple times in attempts to stop the water leak due to cracked plastic For the sake of refrigerant pressure and cooling mode testing the zone system controls have been disabled and isolated for test mode. Run test equipment in multi-stage heat pump cooling mode and confirm 42° supply temperature Ground loop system is running at 30 psi and 46° in preseason cooling test mode Water furnace 2-in disposable air filter is in acceptable condition at this time. Homeowners have been notified no more filters are on site in the basement. Shut down bo