Full system ultraviolet dye and electronic leak search produced the same results as one month ago however this time upon arrival the system was confirmed with low refrigerant pressure AND a visible oily sludgy discharge dripping on the armaflex of the water lines below the refrigerant King valves inside the split Geo in the basement and was saturated and wet and had to be removed for inspections today Micro leak gel could not detect or pinpoint the leak Electronic testing alerted every time Recharge to full capacity with 1+lb clean recycled r410a Recommend replacing both split system King valves with recovery and reuse of the existing refrigerant 3/4 CPVC drain in attic need a drain trap installed and the threaded mail fitting inthe coil drain pan needs replaced. Seth will prepare estimate with jp after confirming availability of the parts