Performed cooling maintenance on a Bryant AC system Blower speed on high 0.7"wc total external static = 1090CFM actual airflow delivery 0.3" drop across the filter when brand new 0.13" drop across evaporator coil Blower is in OK condition Drain is clear 17⁰ delta T across evaporator coil 10⁰ subcool Capacitor tested 39.9/4.6 Removed top of outdoor unit and washed Condenser coil from the inside-out. System is operating within factory specs at this time.