2011 American standard AC cooling maintenance Outdoor fan not running Failed capacitor Replaced 30/5 cap Checked charge, spec is 10⁰ subcool, running 0⁰ Added 1lb R410a, system running 10⁰ subcool now Filter new Drain is long, put treatment tablets in the drain line System is operating within factory specs at this time.