Cooling preventative maintenance performed Check filter - 16x25x1 due soon Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD -40+5 @ 40+5 Check OD fan Amp - 0.66 Check compressor Amp - 6.12 Verify pressures and HP-SC/LP-SH 282/10.4\124/2° Delta T - 18° The Air handler and AC are in optimal running conditions.