Cooling preventative maintenance performed Check filter - 16x25x1 clean Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 45/5 @ Check OD fan Amp - 1.10 @ 0.79 Check compressor Amp - 17.9 @ 11.12 Verify pressures and HP-SC/LP-SH 290/2° \ 127/11° Delta T - 21° The Air handler and AC are in optimal running conditions.