Cooling preventative maintenance performed Check filter - 16x20 washable clean today Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 35+5 @ 34.12+4.75 Check OD fan Amp - 0.55 Check compressor Amp - 5.16 Verify pressures and HP-SC/LP-SH 285/15° \ 140/19° Delta T - 18° The Air handler and AC are in optimal running conditions.