Jeramie T.

Jeramie T.


Job Checkin

System not operating upon arrival. Discovered 60a and 30a breakers OFF at air handler.Engaged breakers and System became operational. AMP Draw on ecm blower .9a and heating elements 20.1a. Discharge air 123° with intake of 51°. CYCLED system multiple times and no issues. System is operating normal at this time.Filter 20x25x1 and like new.Contacters are burnt needs replacement single and dual in air handler.