I performed cooling maintenance today on a Carrier system. Upon arrival, the system was fully operational. I proceeded to test all electrical, mechanical and safety systems. All electrical components tested in the ranges, including the compressor with no signs of damage. I cleaned the outdoor coil and verified that the air filter was still clean. Filter size: 20x25x5 Merv 16 The system has a high static pressure (air stream blood pressure) which can lead to premature blower motor failure. The main cause of high static pressure is ductwork. Upon departure system is fully operational in cooling mode with optimal temperature differentials. Thank you for choosing Cool Air Solutions and being a Comfort Club member!

I performed cooling maintenance today on a Carrier system.
Upon arrival, the system was fully operational.
I proceeded to test all electrical, mechanical and safety systems.
All electrical components tested in the ranges, including the compressor with no signs of damage.
I cleaned the outdoor coil and verified that the air filter was still clean. Filter size: 20x25x5 Merv 16
The system has a high static pressure (air stream blood pressure) which can lead to premature blower motor failure. The main cause of high static pressure is ductwork.
Upon departure system is fully operational in cooling mode with optimal temperature differentials.