Service call that the system was not cooling. Upon arrival found the outdoor unit was not running. Inspected components and tested capacitor. Dual Capacitor had failed. Replaced 45/5 Mfd Dual Capacitor and put system in operation. Measured refrigerant charge and found unit to be low on charge. Added 4lbs of 410-A Refrigerant to system, charging by Superheat. Checked Blower Motor Capacitor and Air Filter on system and inspected components. After adding refrigerant system was running with a 16 Degree Supply/Return Air Differential. System is operating but is overall in poor condition. The blower compartment is very dirty, the outdoor fan motor is very rusted which could lead to failure, and the system has a known refrigerant leak. Due to age and the overall condition of system would recommend replacement of the Gas Furnace/AC system.