520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.


Local Reviews
for lafayette hill, pa


Job Locations
for lafayette hill, pa

Kurt M.

Kurt M. Job Checkin

Installed Aprilaire 2410 Filtration System. Piped intake to furnace. Heat tune up for 100KBTU natural gas Payne furnace. Made call for heat from thermostat. Measured temperature rise. Measured static pressure. Checked flame rectification circuit. Measured hot surface igniter ohms. Checked all controls, wiring, electric motors and components. Combustion draft test: Good Inspection of heat exchanger, burners and igniter: Good Furnace is working fine at time of maintenance. Water hardness test 16 gag. Household of 4.


Brian B.

Brian B. Job Checkin

Checked no heat complaint, found thermostat set to heat and 65 reading 65. Raised temperature, started furnace, checked water safety ok. Checked limit and safety switches. Checked air filter ok.


Shawn R.

Shawn R. Job Checkin

Installed blower control board, tested system for operation, attached retrofit sticker to unit. Inspected drain pan, no signs of damage to drain pan.


Shawn R.

Shawn R. Job Checkin

Did heating tune up, checked burners,flame sensor and igniter, necked temperature difference, checked and replaced filter. Checked blower amp draw, inducer amp draw, inspected drain pan. Preformed combustion analysis. System is working correctly at this time.


Barry P.

Barry P. Job Checkin

AC Tune Up: 3.5 Ton Anana AC system. 20F temp split. Tested pump, cleaned EZ trap. 7 Subcool while system was running in low (dehum) fan speed; good. Both coils are in good condition. All electric motors and components ok. Refrigerant pressures/subcooling ok. Compressor Amos/indoor amps/outdoor voltage ok. All field and manufacturer wiring ok. System is operating well at the time of this tune up.


Chris B.

Chris B. Job Checkin

Performed Precision Heating Tune Up on Amana Gas Furnace system. Replaced 16x24x1 Air Filter. Cleaned Condensation Pump and all drain lines on Furnace. Inspected Electrical components and tightened all connections. Inspected Burners, Ignitor, and Flame Sensor. Visually inspected Interior of Heat Exchanger from the Burners. Some rust forming inside the Tubing walls but no signs of cracks or damage at this time. Put system into operation and tested in Low Stage and High Stage Heating. Performed Combustion Testing in both stages and measured Gas Pressures. Adjusted gas pressures within standards to enhance combustion readings. System operating to standards upon completion.


Kurt M.

Kurt M. Job Checkin

Performed 6 month inspection on amana gas furnace. Checked 16x24x1 air filter is ok. Checked flame sensor and blew out condensate drain tubing. Checked gas pressure in both high and low fire. Checked all electrical conections and components. Performed combustion test. System is working fine at time of inspection.


Paul W.

Paul W. Job Checkin

Installed a new furnace in existing location. Put furnace on feet and put new coil on top of furnace. Adapted supply duct as need and reused existing return drop and filter elbow. Taped and sealed all duct work. Ran new copper lines to ac unit . Installed a new ac on a new plastic pad on top existing concrete pad. Installed a new disconnect box and whip to unit . Brazed and pressure tested all joints. Pumped unit up to 350 psi and sprayed with bubbles . Let vacuum down to 168 microns. Installed a new ez trap condensate drain and ran tubing over to discharge pipe. Modified gas piping to all hard piping and sprayed with bubbles to leak check. Removed old humidifier and patched hole. Taped and caulked all penetrations into the house . Cut back flue piping and re-ran pipe. Installed a new t6 lyric thermostat. Checked charge and added refrigerant as needed. Delta t 24. System operating as it should at time of install.


Chris B.

Chris B. Job Checkin

Performed Precision AC and Heating Tune Up on the Goodman System. Replaced 16x24x1 Air Filter. Cleaned Out all Condensation Drain Lines. While testing Electrical Components, found the Blower Capacitor and the Dual Capacitor we’re testing below rating. When testing Combustion Levels of Furnace found Combustion Levels to be elevated higher than normal. The Furnace was also cycling on/off periodically on High Limit. After further diagnosing the Furnace found the Inducer Motor Assembly was decaying and there was rust present indicating that it was not sealed properly and was leaking. If this is not sealed properly, it could be elevating the Combustion Readings. The Inducer Motor and Assembly would have to be replaced and the system retested. Please note that there still could be further issues with the system, or the system could still experience the High Limit cycling after replacing the Motor. Also spoke with Homeowner about concerns with the Flexible Gas Pipe and the leaking Vent Pipe