Rob  S.

Rob S. Job Checkin

Replaced outdoor 3 pole contactor. Tested system. System is low on refrigerant, approximately 4 to 6 pounds of R22. System will freeze if allowed to run. Diagnostics photo attached. Unknown how long system has been running with low refrigerant levels. Amp draw is low and superheat is high, which are both symptoms of a system running with low refrigerant levels. The compressor sounds like it’s been running with low refrigerant levels for a significant period of time. I initially thought the compressor was running backwards due to the vibrations and sounds of the system running. Checked to ensure voltage was in phase and it was. System is an R22 unit from 2007. Possibility of total compressor failure after adding refrigerant is high. Factory charge of unit is 10 pounds with an additional 1-2 pounds to account for line set and evaporator Due to cost of R22 refrigerant and likelihood of future part failure, recommend system replacement


Rob  S.

Rob S. Job Checkin

Arrived to No Cool Identified faulty 3 amp fuse on control board. 3 amp fuse is faulting due to outdoor contactor failure. Video attached. Need to replace 3 pole contactor. Estimate included Outdoor unit disconnect off at outdoor unit Indoor unit off at Breaker #8


Keith D.

Keith D. Job Checkin

Quoted in hvacbizpro and emailed


Rob  S.

Rob S. Job Checkin

Arrived to No Cool System has multiple issues 1. Evaporator drain pan is rusted to the point water is leaking down furnace and into emergency drain pan 2. Emergency drain pan has had drain connector destroyed and no longer has a drain. This is the location that water that is leaking into emergency pan is leaking onto ceiling 3. Blower motor is extremely dirty causing low airflow 4. System is overcharged with R22 refrigerant. More than likely, the system was freezing due to low airflow so refrigerant was added to prevent this freezing Photos attached