Josh J.

Josh J. Job Checkin

Completed inspection on attic system. Electrical connections are tight. Blower wheel and evap coil are clean. Blower motor and heater packs amping within specs. Cleaned and flushed drain line. Ensuring water safeties functioning properly. Unit is level and draining properly. All ductwork is tight and secure. Reassembled system and proceeded outside. Completed inspection on outdoor unit. Electrical connections are tight. Compressor, cond fan, contractor, cond cap all within specs. Washed cond coil. Pressures are within specs of charging chart. Found the pump ups for outdoor unit are cracked and broken. Suggest having replaced. Completed water heater flush.