Club A/C Rejuvenation: checked air filter and is dirty. Outdoor unit was not running at first sight. Indoor fan is clean and spins with no obstructions. Checked evaporator coil and is clean. Drain pan is a little dirty. Checked electrical connections and are tight. Indoor unit has two voltage enhancement systems. Voltage enhancement system has a factory spec of 10uf and reads 8.6uf and is within allowable fault. Second voltage enhancement system has factory spec of 5uf and reads 4uf and is within allowable fault. Supply has a temperature of 51 degrees and a return of 68. Has a delta t of 17 degrees. Outdoor unit: outdoor unit came on after switching the emergency shut off switch back on from inside. Cut down weeds around outdoor unit it. Brushed off electrical compartment. Outdoor voltage enhancement system has a factory spec of 45/5uf and reads 35/4.9 and is not within allowable fault. Bottom of the unit on the inside is clean. Fan spins with no obstructions. Outdoor v