Ac club rejuvenation: Delta T was 18. Air filter was extremely dirty so I told customer and they will get more. Air movement system was dirty so I cleaned off. All wiring was clean and secure. Drain line system was clean and clear. Cleaned off inside and outside of indoor unit with proper cleaner and wipes. Both indoor voltage enhancement systems were testing below factory spec which were 8.3uf and 3.8uf. factory spec was 10uf and 5uf. Outdoor Voltage enhancement system was running at 43.9/4.7uf. factory spec is 45/5uf. Voltage gateway system was clean and clear of all debris and signs of concern. Cleaned off inside and outside of outdoor unit. System was up and running at normal operation at the end of the visit.