Delta T is 20 degrees. Leak searched coil and found no leaks. Cleaned out debris from bottom of unit. Turbo voltage enhancement system is within factory spec. Air circulation system was dirty so I brushed it off. Air circulation voltage enhancement system is not within factory spec with a rating of 12.5uf actual is 11.3uf. this should be replaced. Coils are clean. WD40 wipedown on the unit. RLA and FLA amps are within factory spec. Purged water removal system.