Discovered airflow issue in wall from furnace to 2nd floor supply trunk going to 3rd floor. 0.0IWC in 2nd floor bathroom trunk and 0.40IWC at furnace supply. Unit has a broken connection or kinked connection behind drywall. Advised Kevin to either cut out and find issue or invest in a minisplit for upper level Needs quote for minisplit on 3rd level