725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Job Locations
for carroll, oh


Map of Carroll OH
Nate G.

Nate G.


Job Checkin

Furnace cycling on high limit. Pulled and cleaned the blower Brush cleaned and vacuumed the secondary heat exchanger fins Adjusted temperature rise Partially closed down the humidifier bypass damper Tested incoming air into the dehumidifier, it is 28% relative humidity. Dehumidifier is set to 45%. No issues suspected with it at this time.