Diagnostic on AC system Found that airflow setting was on factory setting at speed 18 and running with a TESP of 1.5inwc and no measurable CFM as furnace airflow chart only reads to a TESP of 1.0inwc. Proper airflow setting is at speed 10 with a TESP of 0.72inwc and approximate CFM of 980 for the 2.5T AC/Coil system. System is also slightly overcharged with a subcool measurement of 13.5-14F when data plate calls for a 10F Subcool with a +/-3F leniency. Diagnostic on Furnace system Upon initial startup, found that propane kit had not been properly installed and is missing parts/safety features such as the low pressure switch. Manifold pressure was reading 5inwc. Shut down heating system as it is possibly unsafe to operate without propane kit being confirmed as properly installed or redone with a new kit. We will put together a quote for a propane kit installation to verify proper installation and setup for safe operation. Furnace install notes Found that filter rack is not securely in

Diagnostic on AC system
Found that airflow setting was on factory setting at speed 18 and running with a TESP of 1.5inwc and no measurable CFM as furnace airflow chart only reads to a TESP of 1.0inwc. Proper airflow setting is at speed 10 with a TESP of 0.72inwc and approximate CFM of 980 for the 2.5T AC/Coil system. System is also slightly overcharged with a subcool measurement of 13.5-14F when data plate calls for a 10F Subcool with a +/-3F leniency.

Diagnostic on Furnace system
Upon initial startup, found that propane kit had not been properly installed and is missing parts/safety features such as the low pressure switch. Manifold pressure was reading 5inwc. Shut down heating system as it is possibly unsafe to operate without propane kit being confirmed as properly installed or redone with a new kit. We will put together a quote for a propane kit installation to verify proper installation and setup for safe operation.

Furnace install notes
Found that filter rack is not securely in