2023 Bryant Heat Pump running in great condition. Air filter rack labeled 16x20x1 can only fit 16x19.5x1 air filter. Did not habe any in stock on van. Will need to order one and drop off. Current 16x19x1 air filter is adequate for keeping the coils clean. Flush drain pan and drain trap. Run test unit in cooling mode from thermostat. Delta t of 20F with supply temp of 55F. Refrigerant pressures are within spec. Outdoor coils are in clean condition. Outdoor fan motor and compressor are operating within specs. System is operating properly, efficiently and ready for Summer.