Upon arrival found outdoor condenser coil, extremely clogged with dust and lint. Washed outdoor coil checked refrigerant pressures discovered unit low on refrigerant charge 2 pounds or 410 a got sub cool to 10° at 300 psi add leak stop and dye unit went from 6° delta T to 18°