Upon arrival and initial inspection the running refrigerant pressures are reflecting a nearly empty system at 47 PSI suction. Based on information provided by Atlas Butler a on the spot refrigerant leak search was performed with electronic detection and microleak gel detectors however nothing could be confirmed in the area described by them at the evaporator coil. 6 year old icp/adp has a refrigerant leak that requires alternative methods of leak detection. Homeowners have decided to recharge the equipment and begin the multi-step process of ultraviolet dye detection. Refrigerant has been recharged to full capacity and UltraViolet dye with leak stop has been added to the system. Recommended initial ultraviolet inspection in 30 to 60 days to establish a baseline for a rate of leakage. running refrigerant pressures will be tested at the same time 69 Oz new r410a refrigerant required for today's recharge to achieve 10 subcooling at factory specs at 131 and 258 PSI running Single dose