Second floor condenser had locked up fan motor bearings Install Century 42y 1/5 hp outdoor fan motor, reuse existing fan blades, install new 45 + 7.5 440 volt power supply, reattach existing compressor super boost hard start kit Water flush both condenser coils Both condensers are 6 in below recommended grade and at least three inches in the mulch beds. After water flushing both systems, the standing water was above the king valves of both units. *Recommend homeowner resolve drainage issues pooling against the house foundation **Recommend Westin Air raise and re-level both condensers with new permipads to meet current building installation requirements to grade