Cooling preventative maintenance performed 92° outside 74° inside Check filter - 20x25x4 Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose - filthy had to pull cage Check capacitor MFD - 45+5 @ 44.43+4.82 Check OD fan Amp - 11.1 Check compressor Amp - 0.62 Verify pressures and HP-SC/LP-SH 10° subcool @389psi Delta T - 22° The Air handler and AC are in optimal running conditions.