-Master bedroom suite 2015 NVV036 System has 15 x E71 charge loss service codes and is currently in hard lockout After code reset and run test refrigerant pressures are extremely low running at 230 & 92 Fresh refrigerant oil is visible on the evaporator coil in the front right hand corner Recharge only with 3.5 lb new r410a for temporary cooling until permanent repairs are special ordered and installed 7 Series air coil needs replaced -Main house system The Bluish green liquid leaking is ground loop antifreeze. A brass fitting located in the discharge line flushing port has a crack through the metal and needs replaced. 1 inch quarter turn brass ball valve (see pics) Seth will discuss warranty repairs with JP and prepare the estimate ASAP