Gas meter locked out for leakage beyond the stop cock of the furnace During inspection today no gas pressure is available for micro gel leak detection or electronic detection. Based on test results and photos provided to me by third party all indications are that the gas valve is leaking through and not closing tightly. 100% positive identification of the leak with no gas pressure will require a gas line plumber performing a pressure test. Option two replace gas valve and notify gas supplier that the repair has been completed. After gas pressure is reestablished an additional visit will be required to set the manifold pressures of the two-stage intermittent pilot gas valve The December 2004 TempStar high efficiency LP propane gas multi-stage equipment is in very poor neglected condition with extensive wear and tear and water damage that needs immediate attention. Such items include plastic heat exchanger collector box with micro cracks leaking water, The burners are rusted and c