10-year-old water furnace premier branded in Trane Multiple issues unable to be repaired by comfort Express Initial test run failed to start the compressor and locked out on service code 6 on comforter alert indicating open start windings 440 volt compressor power supply set to 45 UF capacitor reading 10.9 Installed new turbo 200 compressor capacitor At the same time it was discovered that all three switch banks of the replacement control board were set to the factory standard Set all three Banks of dip switches designed for two stage with hot water generator and ECM 1\2hp motor Run test all equipment including refrigerant pressures and test antifreeze. 0.992 indicates a week or degraded mixture of alcohol antifreeze and freeze protection to roughly +25° Refrigerant pressures temperatures temperature drops and pressure drops all exactly within book specs with no questions Reattach existing low pressure switch that was bypassed by the previous company Recommend alcohol rejuvenat