2024 Trane Xzr AC running in new condition. 20x25x1 air filter is new today. Visual inspection of indoor coil. Check cooling blower speed and confirm for the proper 1000cfm for 2.5 ton AC. Run test unit in cooling mode from thermostat. Delta t of 20F with supply temp of 54F. Refrigerant pressures are within spec. High 300psi with 11F SC, low 130psi with 12F SH. Outdoor coils are in clean condition. Dual ran capacitor is within spec. Outdoor fan motor and compressor are operating within Amp draw specifications. System is operating properly, efficiently and ready for Summer.